ME HotelM&E AI
Home › Standards › GB 50242-2002 › 第4.2.6条

GB 50242-2002 第4.2.6条 Code for Acceptance of Construction Quality of Building Water Supply, Drainage and Heating Engineering

Indoor water supply给排水

GB 50242-2002 第4.2.6条

| **** | The surface quality of welds on pipes and pipe fittings shall meet the following requirements: the weld profile dimensions shall comply with the drawings and process documents; the weld reinforcement shall not be lower than the base metal surface, and the weld shall transition smoothly to the base metal; the surfaces of the weld and heat-affected zone shall be free from defects such as cracks, lack of fusion, incomplete penetration, slag inclusions, arc craters, and porosity. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.