GB 50242-2002 第3.2.12条
| | After radiators are assembled in groups, and before installation of radiators delivered as complete units, a hydrostatic test shall be performed. Where the design does not specify, the test pressure shall be 1.5 times the working pressure, but not less than 0.6 MPa. |