GB 50974-2014 第13.1.11条
| **** | Fire water tank commissioning: The effective capacity of the high-level fire water tank shall meet the water demand for the first 10 minutes of a fire (for a Class I high-rise public building such as a hotel, it shall be no less than 18 m³); the outlet pipe shall be provided with a check valve to prevent water backflow when the fire pump is running. |