GB 50974-2014 第13.1.8条 Technical code for fire protection water supply and hydrant systems

Commissioning消防工程

GB 50974-2014 第13.1.8条

| **** | Fire hydrant commissioning: The solid water column of the test hydrant (usually installed on the roof or the most unfavorable floor) shall not be less than 10 m (hotel buildings are classified as high-rise civil buildings, and shall not be less than 13 m). |