ME HotelM&E AI
Home › Standards › GB 50974-2014 › 第13.1.6条

GB 50974-2014 第13.1.6条 Technical Code for Fire Protection Water Supply and Hydrant Systems

Commissioning消防工程

GB 50974-2014 第13.1.6条

| **** | Pressure-reducing valve commissioning: for proportional pressure-reducing valves, the ratio of inlet pressure to outlet pressure should not exceed 3:1; for adjustable pressure-reducing valves, the pressure difference between inlet and outlet should not exceed 0.4 MPa. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.