GB 50974-2014 第13.1.5条
| **** | Pressure-maintaining pump commissioning: Before simulating the start of the fire main pump, the pressure-maintaining pump should be able to start and stop automatically; the design pressure should meet the hydrostatic pressure requirement at the most unfavorable point of the system (typically 0.15 MPa for hotels). |