GB 50974-2014 第12.3.10条
| **** | After the fire water supply system is installed, system commissioning shall be carried out. For hotel buildings, commissioning shall focus on the start/stop of fire pumps (including automatic, manual and remote start), the start/stop pressures of the jockey pump, and the effective water column and flow rate of the hydrant at the most unfavorable point. |