GB 50974-2014 第11.0.17条 Technical Code for Fire Protection Water Supply and Hydrant Systems

Control and Operation消防工程

GB 50974-2014 第11.0.17条

| **** | The automatic transfer time between the dual power supplies of fire pumps shall not exceed 2s; when switching between one power supply and engine-driven power, the transfer time shall not exceed 15s. Hotel buildings shall ensure the reliability of the power supply to fire pumps. |