GB 50974-2014 第11.0.9条 Technical code for fire protection water supply and hydrant systems

Control and Operation消防工程

GB 50974-2014 第11.0.9条

| **** | The fire pump control cabinet shall be provided with a mechanical emergency pump-start function, and shall ensure that when the control circuit inside the control cabinet fails, personnel with management authority can start the fire pump in an emergency. During mechanical emergency starting, the fire pump shall be ensured to operate normally within 5 min of the alarm. |