GB 50974-2014 第8.1.4条 Technical code for fire protection water supply and hydrant systems

Pipe network消防工程

GB 50974-2014 第8.1.4条

| **** | The indoor fire water supply pipe network should be arranged in a loop; for hotel buildings, when the design flow of outdoor fire hydrants is not greater than 20L/s and the number of indoor fire hydrants does not exceed 10, it may be arranged in a branch configuration, but hotels usually do not meet this condition. |