GB 50974-2014 第7.4.6条 Technical Code for Fire Protection Water Supply and Hydrant Systems

Fire hydrant system消防工程

GB 50974-2014 第7.4.6条

| **** | For hotel buildings (high-rise), the dynamic pressure at the fire hydrant outlet shall not be less than 0.35 MPa, and the solid water stream of the fire nozzle shall be calculated as 13 m. |