GB 50974-2014 第5.4.7条 Technical code for fire protection water supply and hydrant systems

Water supply facilities消防工程

GB 50974-2014 第5.4.7条

| **** | Fire department connection location: Fire department connections shall be installed outdoors at locations convenient for fire truck use, and the distance from outdoor fire hydrants or fire water tanks should be no less than 15 m and no more than 40 m. Wall-mounted fire department connections should be installed at a height of 0.70 m above ground. |