GB 50974-2014 第5.4.3条 Technical Code for Fire Protection Water Supply and Hydrant Systems

Water supply facilities消防工程

GB 50974-2014 第5.4.3条

| **** | Number of fire department connections: The water supply flow of each fire department connection should be calculated at 10 L/s to 15 L/s. The number of fire department connections for each type of water-based fire extinguishing system should be determined by calculation based on the system design flow; however, when the calculated number exceeds 3, it may be appropriately reduced depending on the reliability of the water supply. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.