ME HotelM&E AI
Home › Standards › GB 50974-2014 › 第5.1.12条

GB 50974-2014 第5.1.12条 Technical code for fire protection water supply and hydrant systems

Water supply facilities消防工程

GB 50974-2014 第5.1.12条

| **** | Fire pump suction requirements: Fire pumps shall use flooded suction. A set of fire pumps shall have no fewer than two suction pipes; when one is damaged or under maintenance, the remaining suction pipes shall still be able to pass the full design fire water supply flow rate. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.