ME HotelM&E AI
Home › Standards › GB 50974-2014 › 第5.1.10条

GB 50974-2014 第5.1.10条 Technical Code for Fire Protection Water Supply and Hydrant Systems

Water supply facilities消防工程

GB 50974-2014 第5.1.10条

| **** | Fire pump standby pump provision: Fire pumps shall be provided with a standby pump whose performance matches that of the duty pump. However, a standby pump may be omitted in the following cases: residential buildings with a building height of less than 54 m, and buildings with an outdoor fire water supply design flow rate of 25 L/s or less. Hotel buildings generally require a standby pump. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.