GB 50974-2014 第5.1.6条 Technical code for fire protection water supply and hydrant systems

Water supply facilities消防工程

GB 50974-2014 第5.1.6条

| **** | Start/stop control of fire pumps: Fire pumps shall be started directly and automatically by signals such as the pressure switch installed on the fire pump discharge main, the flow switch on the outlet pipe of the high-level fire water tank, or the alarm valve pressure switch. The pressure switch in the fire pump room should preferably be wired into the fire pump control cabinet. |