GB 50084-2017 第11.0.4条
| **** | In addition to automatic control, fire pumps shall also be provided with manual control devices (hard-wired direct start) in the fire control room and the fire pump room. |
| **** | In addition to automatic control, fire pumps shall also be provided with manual control devices (hard-wired direct start) in the fire control room and the fire pump room. |