GB 50084-2017 第11.0.3条 Code for Design of Sprinkler Systems

Operation and Control消防工程

GB 50084-2017 第11.0.3条

| **** | The fire pump control cabinet shall be installed in the fire pump room or a dedicated fire pump control room, with a protection rating of no less than IP55; a manually operated direct pump start button connected by a dedicated line shall be provided in the fire control room. |