ME HotelM&E AI
Home › Standards › GB 50084-2017 › 第10.4.1条

GB 50084-2017 第10.4.1条 Code for Design of Sprinkler Systems

Water supply消防工程

GB 50084-2017 第10.4.1条

| **** | Fire department connections shall be located outdoors at positions convenient for fire truck access, and the distance from outdoor fire hydrants or fire water tanks should be no less than 15 m and no more than 40 m. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.