GB 50084-2017 第9.1.23条
| **** | The design flow rate of the hotel building (medium hazard class) system shall be determined based on the total flow rate of sprinklers spraying simultaneously within the operating area at the most unfavorable point, and shall not be less than 20 L/s. |