ME HotelM&E AI
Home › Standards › GB 50084-2017 › 第8.0.10条

GB 50084-2017 第8.0.10条 Code for Design of Sprinkler Systems

Pipe消防工程

GB 50084-2017 第8.0.10条

| **** | The installation of pipe supports, hangers, and sway braces shall meet the following requirements:<br>• Pipes shall be securely fixed; the spacing between pipe supports or hangers shall not exceed the provisions of Table 8.0.10 in the standard (e.g., 3.5 m spacing for DN25 pipes, 6.5 m spacing for DN100 pipes, etc.).<br>• Additional sway braces shall be installed at pipe bends. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.