ME HotelM&E AI
Home › Standards › GB 50084-2017 › 第8.0.3条

GB 50084-2017 第8.0.3条 Code for Design of Sprinkler Systems

Pipe消防工程

GB 50084-2017 第8.0.3条

| **** | Connection methods for automatic sprinkler system piping:<br>• Galvanized steel pipe: threaded connections are recommended when DN≤80; grooved connections (clamps) are recommended when DN>80.<br>• Copper pipe and stainless steel pipe: welding, flanges, or dedicated fittings may be used. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.