GB 50084-2017 第8.0.3条
| **** | Connection methods for automatic sprinkler system piping:<br>• Galvanized steel pipe: threaded connections are recommended when DN≤80; grooved connections (clamps) are recommended when DN>80.<br>• Copper pipe and stainless steel pipe: welding, flanges, or dedicated fittings may be used. |