ME HotelM&E AI
Home › Standards › GB 50084-2017 › 第7.1.6条

GB 50084-2017 第7.1.6条 Code for Design of Sprinkler Systems

Sprinkler layout消防工程

GB 50084-2017 第7.1.6条

| | Except for ceiling-type sprinklers and sprinklers installed below ceilings, for upright and pendent standard coverage sprinklers, the distance between the deflector and the ceiling shall not be less than 75mm and shall not be greater than 150mm. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.