GB 50084-2017 第5.0.13条 Code for Design of Sprinkler Systems

Design parameters消防工程

GB 50084-2017 第5.0.13条

| **** | In hotel buildings, for an **atrium** with a clear height greater than 8 m and less than or equal to 18 m, when non-storage special application sprinklers are used, the sprinkler discharge density shall not be less than **15 L/(min·m²)**, and the operating area shall not be less than **260 m²**. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.