Home › Standards › GB 50084-2017 › 第5.0.11条

GB 50084-2017 第5.0.11条 Code for Design of Sprinkler Systems

Design parameters消防工程

GB 50084-2017 第5.0.11条

| **** | In hotel buildings, for **conference halls and multi-function halls** (classified as other occupancies) with a clear height greater than 8 m and less than or equal to 12 m, the sprinkler discharge density shall not be less than **15 L/(min·m²)**, and the design area of sprinkler operation shall not be less than **160 m²**. |