ME HotelM&E AI
Home › Standards › GB 50084-2017 › 第5.0.1条

GB 50084-2017 第5.0.1条 Code for Design of Sprinkler Systems

Design parameters消防工程

GB 50084-2017 第5.0.1条

| **** | For Moderate Hazard Class I, the sprinkler discharge density shall not be less than **6 L/(min·m²)**, and the design area of sprinkler operation shall not be less than **160 m²**. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.