GB 51251-2017 第9.0.9条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

System Acceptance消防工程

GB 51251-2017 第9.0.9条

| **** | During acceptance of the makeup air system (e.g., hotel basement or inner-zone corridors), the air velocity at the makeup air inlet should be tested (preferably not greater than 3 m/s), and the makeup air volume should be ensured to match the smoke exhaust volume. |