GB 51251-2017 第9.0.6条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

System Acceptance消防工程

GB 51251-2017 第9.0.6条

| **** | During acceptance of natural smoke exhaust facilities (such as hotel exterior windows and roof skylights), check whether their opening method, effective area and manual opening devices are easy to operate. Natural smoke exhaust windows in hotel guest rooms and corridors should be installed within the smoke reservoir. |