GB 51251-2017 第9.3.3条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

Construction and Commissioning消防工程

GB 51251-2017 第9.3.3条

| **** | Smoke exhaust fans shall be installed in a dedicated machine room, and the machine room shall be separated from other areas by partition walls with a fire resistance rating of not less than 2.00 h and floor slabs with a fire resistance rating of not less than 1.50 h. Smoke exhaust fan rooms on the hotel roof or equipment floor shall meet this requirement. |