GB 51251-2017 第9.3.1条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

Construction and Commissioning消防工程

GB 51251-2017 第9.3.1条

| **** | Smoke exhaust valves, smoke exhaust outlets, supply air outlets, fire dampers, etc. shall be installed securely, operate reliably, and be provided with manual, motorized, or interlocked opening functions. Smoke exhaust outlets in hotel guest rooms (if any) and corridor smoke exhaust outlets shall meet this requirement. |