GB 51251-2017 第9.6.2条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

Smoke control system equipment消防工程

GB 51251-2017 第9.6.2条

- **** | Smoke exhaust fans and make-up air fans shall be capable of automatic shutdown at 280℃ and feed back signals to the fire control room. In hotel buildings, kitchen smoke exhaust fans and corridor smoke exhaust fans must meet this requirement.