GB 51251-2017 第9.3.3条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

Smoke control system equipment消防工程

GB 51251-2017 第9.3.3条

- **** | Normally closed smoke exhaust valves (outlets) shall have a reset function and shall be able to open again after reset. In hotel buildings, smoke exhaust valves used for zone control need to have this function.