GB 51251-2017 第9.2.4条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

Smoke control system equipment消防工程

GB 51251-2017 第9.2.4条

- **** | A 280°C smoke exhaust fire damper shall be installed at the fan inlet and interlocked to shut down with the fan. The hotel smoke exhaust system (e.g., where smoke exhaust ducts penetrate fire compartments) must be equipped with this damper.