GB 51251-2017 第4.5.2条 Technical Standard for Smoke Control and Exhaust Systems in Buildings

Smoke exhaust system design消防工程

GB 51251-2017 第4.5.2条

| **** | For **underground** or **above-ground windowless** corridors and rooms in hotel buildings, the makeup air system should prioritize **natural makeup air**; when natural makeup air does not meet the requirements, mechanical makeup air should be used. |