GB 51251-2017 第4.3.2条
| **** | In hotel buildings, the smoke exhaust outlets or smoke exhaust valves of **rooms** (such as guest rooms and meeting rooms) shall be installed at a position **above 1/2 of the clear height**; when installed on a side wall, the distance between their nearest edge and the suspended ceiling shall not exceed 0.5 m. |