GB 50041-2020 第4.3.2条 Boiler Room Design Standard

Boiler system暖通空调

GB 50041-2020 第4.3.2条

| **** | Boiler feed pumps shall include a standby pump; when one pump stops operating, the total flow of the remaining pumps shall meet 1.1 times the hotel's maximum heat load (including heating, air conditioning and domestic hot water). |