GB 50041-2020 第4.2.3条 Boiler Room Design Standard

Boiler system暖通空调

GB 50041-2020 第4.2.3条

| **** | For boilers used in hotel domestic hot water systems, the outlet water temperature shall be determined according to water quality and heat exchange requirements, generally not lower than 60℃, and scald-prevention and water temperature regulation measures shall be provided. |