ME HotelM&E AI
Home › Standards › GB 50041-2020 › 第4.3.3条

GB 50041-2020 第4.3.3条 Boiler Room Design Standard

Boiler room layout暖通空调

GB 50041-2020 第4.3.3条

| **** | Gas and fuel oil pipelines in the boiler room shall be provided with emergency shut-off valves located in easily accessible positions. The hotel boiler room shall be equipped with combustible gas concentration detection and alarm devices interlocked with the emergency exhaust fans and emergency shut-off valves. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.