GB 50041-2020 第4.2.7条 Boiler Room Design Standard

Boiler room layout暖通空调

GB 50041-2020 第4.2.7条

| **** | Facilities unrelated to boiler operation (such as hotel laundry rooms, staff dormitories, etc.) shall not be located within the boiler room. When the boiler room is adjacent to other hotel rooms, the partition wall shall be a fire wall, and no door or window openings shall be provided. |