GB 50041-2020 第4.1.3条 Boiler Room Design Standard

Boiler room layout暖通空调

GB 50041-2020 第4.1.3条

| **** | The boiler room should preferably be located in a dedicated room outside the building or in a standalone building; when it must be located within the main hotel building, it shall not be placed on the floor above, the floor below, or adjacent to densely occupied areas (such as the lobby, restaurant, or banquet hall), and shall be separated from adjacent areas by fire-rated walls. |