GB 50243-2016 第11.4.2条 Code for Acceptance of Construction Quality of Ventilation and Air Conditioning Works

System commissioning暖通空调

GB 50243-2016 第11.4.2条

| **** | The flow deviation of each loop in the air-conditioning water system (such as different floors and different functional zones) from the design flow shall not exceed 15%. Hotels need to make fine adjustments through balancing valves to ensure the cooling/heating effect in each area. |