GB 50243-2016 第11.3.3条
| **** | The deviation between the measured air volume of each air outlet (supply, return, exhaust) and the design air volume shall not exceed 15%. Independent spaces such as hotel guest rooms and meeting rooms shall be commissioned outlet by outlet to avoid airflow short-circuiting or dead zones. |