GB 50243-2016 第11.3.2条 Code for Acceptance of Construction Quality of Ventilation and Air Conditioning Works

System commissioning暖通空调

GB 50243-2016 第11.3.2条

| **** | The measured total system air volume shall not deviate from the design air volume by more than -5% or +10%. For the hotel kitchen exhaust system and public restroom exhaust system, negative pressure and air change rate must be specifically verified. |