GB 50243-2016 第8.7.1条 Code for acceptance of construction quality of ventilation and air conditioning works

Air-conditioning cooling system暖通空调

GB 50243-2016 第8.7.1条

| **** | Refrigeration system trial run: it shall be carried out after the individual trial runs of equipment such as chillers, cooling towers, and pumps have passed; the continuous running time shall not be less than 8 hours, and all system parameters (such as chilled water supply/return temperature difference, cooling water temperature, and pressure) shall be stable within the design range. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.