GB 50243-2016 第8.2.1条 Code for Acceptance of Construction Quality of Ventilation and Air Conditioning Works

Air-conditioning cooling system暖通空调

GB 50243-2016 第8.2.1条

| **** | The installation deviation of refrigeration units (including modular units) shall comply with the standard: allowable deviation of plan position ±10mm, allowable deviation of elevation ±10mm; contact with the foundation shall be tight with no looseness. |