ME HotelM&E AI
Home › Standards › GB/T 50466-2018 › 第4.3.1条

GB/T 50466-2018 第4.3.1条 Code for Thermal Design of Civil Building

Building thermal energy efficiency暖通空调

GB/T 50466-2018 第4.3.1条

| | The heat transfer coefficient and thermal inertia index of the hotel building's exterior walls shall comply with the limits for the climate zone in which they are located: in severe cold regions K≤0.35 W/(m²·K), in cold regions K≤0.50 W/(m²·K), and in hot summer and cold winter regions K≤0.80 W/(m²·K). |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.