ME HotelM&E AI
Home › Standards › GB 50314-2015 › 第4.8.3条

GB 50314-2015 第4.8.3条 Standard for Intelligent Building Design

Design Elements弱电智能化

GB 50314-2015 第4.8.3条

| | Hotel buildings shall be equipped with an energy consumption monitoring system that provides sub-metering of water, electricity, gas, and other energy consumption (metering accuracy not lower than Class 1.0), with a data collection interval of ≤15 minutes, and shall support the generation of energy consumption reports by day, month, and year. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.