Glass self-explosion or seal failure and water ingress in the glass shaft of outdoor panoramic elevators under extreme weather conditions

Expert Q&AEthan Liu · Elevator SpecialistUpdated 2026-05-04
E
Ethan Liu
Elevator Specialist

Glass self-explosion or seal failure and water ingress in the glass shaft of outdoor panoramic elevators under extreme weather conditions

Observation elevators use transparent cars and glass hoistway structures, which differ from ordinary passenger elevators in selection and technical requirements. Outdoor observation elevators face special challenges such as wind load, temperature stress and UV aging. Based on GB 15763.2-2005 "Safety Glass for Building" and JGJ 113-2015 "Technical Specification for Application of Architectural Glass", this paper systematically analyzes the selection and maintenance requirements of glass hoistways for observation elevators.

Article 5.3 of GB 7588-2003 stipulates that glass hoistways and car walls of observation elevators shall use safety laminated glass and have sufficient mechanical strength. GB 15763.2-2005 requires that tempered laminated glass used for observation elevators shall be of 6mm + 0.76mm PVB + 6mm and above. The wind pressure design value shall not be less than 1.5kPa, and weather-resistant silicone sealant shall be selected for joint sealing.

Glass connection methods are divided into point-supported and frame-supported types. The point-supported type uses spider fittings for connection, offering good transparency but costing 50% to 80% more. The frame-supported type uses metal frames for fixing, offering high safety but slightly poorer visual effect. The glass floor of a fully transparent car shall be marked with a standing area to prevent passengers from experiencing discomfort from fear of heights. The drive system is recommended to use permanent magnet synchronous gearless traction machines for smooth operation and low noise.

The speed of outdoor observation elevators is recommended not to exceed 2.5 m/s, and indoor ones not to exceed 3.0 m/s. During operation, the glass hoistway needs to be cleaned once a month for the outdoor part to maintain transparency and aesthetics, with each cleaning costing about 500 to 2,000 yuan. The energy consumption of observation elevators is 10% to 20% higher than that of ordinary elevators of the same specification, because the poor thermal insulation performance of the glass hoistway increases the air-conditioning load.

Maintenance points include monthly inspection of glass panel cracks, scratches and sealant aging, and quarterly inspection of the fastening status of point-supported spider fittings or frame-supported connectors. The sealant on sun-exposed surfaces shall be replaced every 2 to 3 years. When the PVB film shows yellowing or bubbles, the panel shall be replaced immediately. The procurement cost of outdoor observation elevators is 50% to 100% higher than that of ordinary elevators of the same specification.

Engineering experience shows that outdoor observation elevators need to consider wind-resistant design, and speed limitation or shutdown is recommended in strong wind weather. The expansion joints between the glass hoistway and the main structure need to be carefully treated to prevent glass breakage caused by temperature deformation. Low-E coated glass is used in direct sunlight areas to reduce the temperature inside the car. It is recommended to install electric sunshades at the top of the hoistway.

The operation of observation elevators in hotels and commercial complexes also requires consideration of special fire evacuation schemes. Buildings equipped with observation elevators shall have ordinary enclosed stairwells in adjacent areas as evacuation routes in case of fire. Automatic fire sprinkler systems shall be installed in the hoistway of observation elevators to protect the integrity of glass panels in case of fire. The nighttime landscape lighting design shall be coordinated with the overall building lighting system, with LED light strips embedded in the hoistway frame to create a floating effect. The operating cost of observation elevators is about 30% to 50% higher than that of ordinary elevators, but the commercial value and visual appeal they bring far exceed the extra investment. During selection, local climate conditions shall be fully considered, e.g., coastal areas shall consider the impact of salt spray corrosion on glass and metal frames, and severe cold areas shall consider glass icing and temperature difference stress issues and take corresponding protective measures.

The glass hoistway design of observation elevators also needs to consider energy-saving and environmental protection requirements. The use of Low-E insulating glass can significantly reduce the heat transfer coefficient and reduce the air-conditioning load. The shading coefficient of glass panels can be selected between 0.3 and 0.5, which can maintain transparency while controlling solar radiation. Adjustable shading louvers at the top of the hoistway can automatically adjust the shading angle according to the sun angle. The LED lighting system shall adopt inductive control, with lights turning on when people approach and dimming or turning off when people leave, to save electrical energy. The energy consumption monitoring of observation elevators shall be incorporated into the hotel's energy management system for real-time monitoring and optimized operation strategies. In terms of structural safety, the design load of glass panels shall consider the combined effects of wind load, snow load, temperature stress and seismic action. The connection between glass panels and metal frames shall adopt elastic connection design, allowing glass panels to expand and contract freely during temperature changes to avoid breakage caused by stress concentration. The anti-collision design of glass panels also needs attention, with protective railings or buffer pads installed on the outside of the glass to prevent impact from external objects. The daily inspection of observation elevators shall include surface temperature detection of glass panels and status inspection of sealing strips, and abnormalities shall be handled promptly to prevent small problems from developing into major failures.

The glass hoistway design of observation elevators also needs to consider energy-saving and environmental protection requirements. The use of Low-E insulating glass can significantly reduce the heat transfer coefficient and reduce the air-conditioning load. The shading coefficient of glass panels can be selected between 0.3 and 0.5, which can maintain transparency while controlling solar radiation. Adjustable shading louvers at the top of the hoistway can automatically adjust the shading angle according to the sun angle. The LED lighting system shall adopt inductive control, with lights turning on when people approach and dimming or turning off when people leave, to save electrical energy. The energy consumption monitoring of observation elevators shall be incorporated into the hotel's energy management system for real-time monitoring and optimized operation strategies. In terms of structural safety, the design load of glass panels shall consider the combined effects of wind load, snow load, temperature stress and seismic action. The connection between glass panels and metal frames shall adopt elastic connection design, allowing glass panels to expand and contract freely during temperature changes to avoid breakage caused by stress concentration. The anti-collision design of glass panels also needs attention, with protective railings or buffer pads installed on the outside of the glass to prevent impact from external objects. The daily inspection of observation elevators shall include surface temperature detection of glass panels and status inspection of sealing strips, and abnormalities shall be handled promptly to prevent small problems from developing into major failures. Hoistway cleaning of observation elevators is a continuous expense in operation. It is recommended to use electric lifting platforms with professional cleaning tools for regular cleaning, with the cleaning frequency determined according to local air quality conditions, generally 1 to 2 times per month. Anti-fouling treatment of glass panels can use nano self-cleaning coatings to reduce stain adhesion and reduce cleaning frequency. The operation management plan of observation elevators under severe weather shall be incorporated into the hotel's emergency response plan, including speed limitation or suspension standards for strong wind, heavy rain, heavy fog and high temperature weather. The emergency rescue plan for observation elevators shall consider visual comfort and rapid rescue measures for passengers when the elevator stops in mid-air, and be equipped with dedicated rescue tools and communication equipment to ensure passenger safety and comfort.

The brand image value of observation elevators in hotels cannot be ignored. A beautifully designed observation elevator can become an iconic feature of the hotel, attracting guests to take photos and share them on social media. The night lighting design of the observation elevator should be uniformly designed according to the hotel's overall lighting scheme, with LED light strips embedded in the hoistway frame providing soft and even light, creating a floating light-and-shadow effect at night that enhances the building's recognisability. The interior decoration of the observation elevator car should match the hotel's decoration style, and a car with a transparent glass floor can be selected to enhance the visual experience. A rest area and information boards should be provided on the observation platform floor of the observation elevator, introducing the elevator's technical parameters and information about the surrounding scenery. The operating speed of the observation elevator should not be too fast; it is recommended to control it between 1.5 and 2.5 m/s to give passengers sufficient time to enjoy the view. The operating revenue of the observation elevator can be diversified through observation ticketing and naming-rights sponsorship. Although the maintenance cost of the observation elevator is relatively high, the brand premium and commercial value it brings far exceed the investment. It is recommended that hotels fully consider its commercial operating model when planning an observation elevator. The passenger safety protection measures of the observation elevator should be higher than the standards for ordinary elevators. Multi-angle cameras should be installed in the car to cover the entire car area, with monitoring images transmitted in real time to the security centre. An emergency communication device and SOS button should be provided in the car so that passengers can contact the control centre with one touch. Fire extinguishers and emergency lighting devices should be provided in the car to protect passenger safety in emergency situations. Safety warning signs should be provided on the glass panels of the car to remind passengers not to lean against the glass. The observation elevator should be equipped with a backup power system that can automatically switch over during a mains power failure to continue operation or run at slow speed to the nearest floor and open the doors. Operation should be stopped immediately if any safety hazard is found.

The anti-corrosion design of outdoor observation elevators is particularly important in coastal areas. The salt spray in sea breezes is highly corrosive to metal frames and glass connectors, so corrosion-resistant materials such as stainless steel or aluminium alloy should be used. The surface treatment of the metal frame should adopt a dual anti-corrosion process of hot-dip galvanising plus fluorocarbon coating. Glass connectors should be made of stainless steel, and bolts and nuts should use lock washers to prevent loosening due to vibration. Silicone sealant with excellent weather resistance should be used, with a service life of no less than 10 years. The wind-resistant design of outdoor observation elevators is equally important; the operating speed limit under strong wind conditions should be determined according to the specific parameters of the elevator and local meteorological conditions. It is recommended to equip an anemometer to monitor wind speed in real time, and automatically reduce the operating speed or suspend operation when the wind speed exceeds the design limit. The lightning protection of the observation elevator should comply with the requirements of the code for lightning protection design of buildings, with air terminals installed at the top of the hoistway and the metal frame reliably earthed. Through comprehensive anti-corrosion, wind-resistant and lightning protection design, the safe and reliable operation of outdoor observation elevators in harsh environments is ensured.

The comprehensive benefit analysis of observation elevators should include both direct benefits and indirect benefits. Direct benefits come from observation ticketing revenue and naming-rights sponsorship, while indirect benefits come from brand value enhancement, guest satisfaction and social media exposure. Comprehensive assessment shows that the return on investment of observation elevators is usually higher than that of ordinary elevators, especially in tourist cities and urban landmark buildings. The selection of observation elevators should be combined with the overall design concept of the building and the characteristics of local tourism resources to create a unique visual experience and brand memory point. The operation and management of observation elevators should be the responsibility of a professional team, with standardised operating processes and service standards formulated. It is recommended that hotels build the observation elevator as a core competitiveness and enhance the hotel's brand value and market competitiveness through high-quality operating services.

It should be emphasised that the safe and reliable operation of the observation elevator is the prerequisite for all operating activities, and regular inspection and uninterrupted maintenance are the basic guarantees for its normal operation. The safe and reliable operation of the observation elevator is the prerequisite for all operating activities, and regular inspection and uninterrupted maintenance are the basic guarantees for its normal operation. Conduct comprehensive inspections of glass panels, metal frames and the drive system on a regular basis, and deal with any hidden hazards promptly to ensure the elevator is always in optimal condition and provide passengers with a safe and comfortable observation experience.

The safe and reliable operation of the observation elevator is the prerequisite for all operating activities, and regular inspection and maintenance are the basic guarantees for its normal operation; preventive measures must be taken. Only by adhering to standardised maintenance management can the long-term safe and reliable operation of the observation elevator be ensured.

Standard reference

GB 15763.2-2005JGJ 113-2015GB 7588-2003