Requirements for hotel fire elevators and their differences from ordinary elevators

Elevator engineeringUpdated 2026-05-13

I am elevator expert Ethan Liu, specializing in elevator selection, installation, commissioning, and special equipment management. The fire elevator setup requirements you mention…

Requirements for hotel fire elevators and their differences from ordinary elevators

I am elevator expert Ethan Liu, specializing in elevator selection, installation, commissioning, and special equipment management. The fire elevator setup requirements you mentioned and their differences from ordinary elevators are a critical safety design aspect in hotel projects. Fire elevators undertake the key tasks of personnel evacuation and firefighter rescue in emergency situations such as fires, and their setup must strictly comply with national codes to ensure the safety of life and property. Below, I will analyze this topic in detail in conjunction with GB7588, GB/T 10060, and fire protection-related codes.

Fire Elevator Setup Requirements


According to Article 7.3 of the "Code for Fire Protection Design of Buildings" (GB 50016-2014, 2018 edition), the setup of fire elevators must meet the following core requirements:

Differences Between Fire Elevators and Ordinary Elevators


According to GB7588-2003 (including Amendment No. 1) and GB/T 10060-2011, there are significant differences between fire elevators and ordinary elevators in design, function, and use:
1. Design Codes: Ordinary elevators are designed according to the general standard GB7588, focusing on daily comfort and efficiency; fire elevators must simultaneously satisfy GB50016 and GB/T 26465 (Safety Code for the Construction and Installation of Fire Elevators), emphasizing fire resistance, waterproofing, and emergency capability.
2. Functional Requirements: Ordinary elevators are automatically powered off or taken out of service during a fire to prevent smoke spread; fire elevators have fire-resistant, smoke-proof, and waterproof functions, such as smoke exhaust openings in the shaft and better car sealing. Fire elevators are also equipped with backup power and independent control systems to ensure continuous operation during a fire.
3. Usage Scenarios: Ordinary elevators are used for daily personnel transport, with load and speed set according to building use (e.g., hotel passenger elevators are usually 1.0–1.75 m/s); fire elevators are dedicated to firefighting and rescue by firefighters, with a speed of not less than 0.5 m/s and requiring arrival at the top floor within 60 seconds.
4. Structural Differences: Fire elevator shafts require fire compartmentation, and fire doors are provided in the lobby; ordinary elevator shafts have no mandatory fire protection requirements (unless shared with fire elevators). The landing doors and car doors of fire elevators must have fire-resistant performance, while ordinary elevator doors are usually made of ordinary materials.

Practical Engineering Case


I once participated in a five-star hotel project (building height 45 m, 12 floors in total), and encountered a typical problem in the fire elevator setup: the original design shared the shaft between the fire elevator and ordinary passenger elevators. After review, according to Article 7.3.2 of GB50016, an independent shaft was required, and a fire wall with a fire resistance rating of 2 hours was added. During construction, we also found that drainage at the bottom of the shaft was not designed, resulting in a water accumulation risk; subsequently, a sump and drainage pump were added to meet the drainage capacity requirements. During the commissioning stage, the firefighter control function of the fire elevator needed to be interlocked with the fire alarm system to ensure correct signal transmission. In this case, the independent power supply and fire door installation of the fire elevator were key control points, and the project ultimately passed acceptance.

Summary


The setup requirements for fire elevators are strict, and the main differences lie in fire protection, waterproofing, emergency control, and independence, which are the bottom line for safe hotel operation. During design, priority should be given to GB50016 and GB/T 26465, combined with building height, use, and local fire department requirements, to ensure complete functionality. The above are reference opinions. The actual project situation still needs to be further comprehensively evaluated and implemented in combination with specific working conditions, site conditions, and other factors.