Type selection and width calculation of hotel evacuation stairs
I am fire protection expert Alexander Li. The selection of evacuation stair types and width calculations are core elements of hotel fire protection design, directly determining whether occupants can evacuate safely and quickly during a fire. Based on my engineering experience, this is not only a basic requirement for code compliance, but also a lifeline that must be prioritized under the special scenario of high occupant density and complex evacuation paths in hotel operations. An incorrect type or insufficient width may lead to evacuation congestion, egress delays, and even stampede accidents.
Detailed Analysis
1. Selection of Evacuation Stair Types
The type of evacuation stair is primarily determined by building height, occupancy function, and fire compartmentation. According to the Code for Fire Protection Design of Buildings (GB 50016-2014, 2018 edition):
- Enclosed stairwell: Applicable to multi-storey hotels (Class II high-rise public buildings with building height ≤32m). For example, in a four-star hotel project I worked on, the building height was 24m, and an enclosed stairwell was selected, separated by Class B fire doors and provided with natural smoke exhaust windows, meeting the requirements of Article 5.5.13.
- Smoke-proof stairwell: Applicable to Class I high-rise hotels (building height >50m) or Class II high-rise hotels with building height >32m. For example, a five-star hotel with a height of 80m was designed with smoke-proof stairwells, with a vestibule area ≥6m² (shared vestibule ≥10m²) and a mechanical pressurization air supply system, in accordance with Article 5.5.12. Smoke-proof stairwells can effectively block smoke and ensure the safety of evacuation routes.
- Outdoor evacuation stair: May serve as an auxiliary evacuation facility, but attention must be paid to its width and fire resistance rating (≥0.25h), and it shall not be used for primary evacuation. For example, a renovated hotel added an outdoor stair due to space constraints, but it served only as a backup.
2. Evacuation Stair Width Calculation
Width calculation is based on occupant load and evacuation time. According to Article 5.5.21 of GB 50016:
- Occupant density: 0.5 persons/m² (floor area) for hotel guest room areas; 1.0 person/m² for public areas (restaurants, meeting rooms). For example, for a hotel guest room area of 1000m², the occupant count is 500.
- Width index per 100 persons: For buildings of fire resistance Class I and II, the required net width per 100 persons is 1.0m (above-ground floors). Calculation formula: Total width (m) = Total occupants / 100 × width index per 100 persons.
- Minimum net width: Evacuation stair net width ≥1.1m (public buildings); evacuation stairs in hotel guest room areas are often 1.2m. For example, a hotel with 300 occupants per floor: calculated width = 300/100×1.0 = 3.0m, requiring 2 stairs (1.5m each).
3. Key Code Clauses
- GB 50016 Article 5.5.12: Class I high-rise public buildings shall be provided with smoke-proof stairwells.
- Article 5.5.13: Multi-storey buildings (height ≤32m) may be provided with enclosed stairwells.
- Article 5.5.18: Evacuation stair net width ≥1.1m, door net width ≥0.9m.
- Article 5.5.21: Calculation of width index per 100 persons.
- Article 6.4.1: Combustible gas piping shall not be installed within stairwells.
- GB 50261-2017 (Code for Construction and Acceptance of Automatic Sprinkler Systems), although not directly concerning stairs, emphasizes sprinkler coverage within fire compartments, indirectly affecting evacuation safety.
4. Engineering Experience and Precautions
- Hotel-specific scenarios: Hotels often need to consider wheelchair users and luggage handling, so stair widths should be appropriately increased (e.g., 1.3–1.5m). In a renovation project, because the stair width was insufficient (only 1.0m), I added an outdoor stair and passed fire performance-based review.
- Smoke-proof stairwell vestibule: The vestibule area must meet code requirements (public buildings ≥6m²) and shall not be occupied by pipe shafts. For example, a hotel failed acceptance because the vestibule was penetrated by a fire pipe; the pipe routing was later adjusted.
- Evacuation signage: Illuminated evacuation direction signs shall be provided within stairwells (spacing ≤20m), with illuminance maintained at ≥5lx.
The above are reference opinions. The actual project situation still needs to be further comprehensively evaluated and implemented in combination with specific operating conditions, site conditions, and other factors.